St. Joseph, MO Finds the Best Solution for Sewer Odors and Corrosion

ECO₂'s case study of St. Joseph, Missouri, where pure oxygen in the Parkway A force main took over from chemical feed to control sewer odors and corrosion.

Details

Publisher
ECO₂

Summary

St. Joseph, Missouri had sewer odors along Parkway A near Mark Twain Elementary School, and chemicals added at the Faraon Street Pump Station were not enough, especially in dry weather. With consultant Burns & McDonnell, the city installed a 4 ft Speece Cone® at the pump station that delivers around 1,600 pounds of dissolved oxygen per day through a 1,400 gpm side stream driven by a 12 horsepower pump, keeping the 24 inch, 10,560 ft force main aerobic.

Key Figures

Questions

What was the problem on Parkway A?

Sewer odors along the parkway near Mark Twain Elementary School; chemicals added at the Faraon Street Pump Station were not enough, especially in dry weather. (PDF page 1) (opens in a new tab)

What system was installed?

A 4 ft diameter Speece Cone at the Faraon Street Pump Station, with a 12 horsepower side stream pump and bulk liquid oxygen storage, delivering around 1,600 pounds of dissolved oxygen per day. (PDF page 2) (opens in a new tab)

Does the system add air or bubbles to the sewer?

No. Only dissolved oxygen is blended back into the force main, in the amount needed to keep the whole length aerobic. (PDF page 2) (opens in a new tab)

Who was the consultant?

Burns & McDonnell, on its third project with ECO₂ after Colorado Springs and Broomfield, Colorado. (PDF page 2) (opens in a new tab)

The Project

Parkway-A Force Main

Location
St. Joseph, Missouri
Application
Wastewater Odor Control
Capacity
1,580 lbs/day
See the Project

In Full

More Key Figures

Four more, each with what it measures and its PDF page.

From the PDF

FigureWhat It Measures
4 ft
Speece Cone diameter (PDF page 2 (opens in a new tab))
24 inch
Force main diameter (PDF page 2 (opens in a new tab))
10,560 ft
Force main length treated (PDF page 2 (opens in a new tab))
3 million gallons/day
Force main flow (over) (PDF page 2 (opens in a new tab))

Full Text as Published

The text as its authors wrote it.
The case study's own words, as published. Its figures are the authors'; the PDF (2 pages) is the original, with the figures, photos and tables drawn as images.

City of St. Joseph, Missouri: Parkway A Odor Control Project

The City of St. Joseph, Missouri is the county seat of Buchanan County and the eighth largest city in Missouri with approximately 77,176 residents as of 2012. St. Joseph is the central service provider for a seven-county area of northwest Missouri and north east Kansas with a combined population of over 155,000.

Jesse James Home and Museum St. Joseph, MO

St. Joseph is located roughly 30-miles north of Kansas City, MO and approximately 125-miles south of Omaha, NE. The town has a rich history that includes Jesse James and the birthplace of the Pony Express.

The purpose of the Parkway A Odor Control Project was to address odors originating from the sewer system along the parkway in the vicinity of Mark Twain Elementary School. Chemicals to reduce odors were being added at the Faraon Street Pump Station. The chemical addition proved to not be sufficient to control the problem, especially during the periods of dry weather.

Mark Twain Elem. School

  • Technology: Pure Dissolved Oxygen for H₂S Prevention
  • Application: Sewer Force Main
  • Location: St. Joseph, Missouri
  • Consultant: Burns & McDonnell
  • Objectives: Prevent Odors; Protect Infrastructure

Force Main H₂S Prevention System

In the August 2, 2018 issue of the City Link (a publication of the City), the City stated the ECO₂ oxygenation system "is both more effective and economical than the current approach in controlling odors."

The consultant for the Parkway A Project was Burns & McDonnell; this is the third project in collaboration with this firm- Colorado Springs, CO and Broomfield, CO- being the first two.

The project details are as follows:

  • 24-inch force main diameter
  • 10,560-feet force main length
  • Over 3 million gallons per day

Results

The resulting ECO₂ system sized specifically for this project and installed at the Faraon Street Pump Station was a 4-ft diameter Speece Cone capable of delivering around 1,600 pounds of dissolved oxygen per day via a carrier stream of only 1,400 gallons per minute (gpm). The side stream pump, which brings raw wastewater from the force main pipe to the Speece Cone and right back into the force main pipe, was only a 12-horsepower pump. Ancillary components included a bulk liquid oxygen storage tank, vaporizer, and other associated oxygen storage equipment. The system dissolves just the precise amount of pure oxygen to maintain aerobic conditions in the entire length of the force main. Only dissolved oxygen is blended back into the force main, no air or bubbles are introduced into the sewer system. The system has been effectively preventing H₂S since 2018.

How to Cite

One line to paste into a report.

St. Joseph, MO Finds the Best Solution for Sewer Odors and Corrosion. ECO₂. Project engineer: Burns & McDonnell. Eco Oxygen Technologies Technical Library. https://eco2tech.com/technical-library/st-joseph-mo-finds-the-best-solution-for-sewer-odors-and-corrosion/

https://eco2tech.com/technical-library/st-joseph-mo-finds-the-best-solution-for-sewer-odors-and-corrosion/

The Next Step

Ask an ECO₂ Engineer

Questions about this case study, or about your own water? An application engineer answers, with the figures.