Lake D.O. Supplementation at Barberton Reservoir in Denver OH

ECO₂'s case study of Barberton's Wolf Creek Reservoir, whose anoxic bottom water let manganese plug the water plant's membrane filters, and the oxygen the city added.

Details

Publisher
ECO₂
Engineer
Burgess & Niple

Summary

The bottom layer of the City of Barberton's Wolf Creek Reservoir is anoxic most of the time, which lets manganese dissolve into the raw water and plug the water plant's membrane filters. In early spring and early fall manganese can exceed 0.200 mg/l for weeks.

Key Figures

Questions

Why did Barberton need to oxygenate its reservoir?

The reservoir's hypolimnion is anoxic most of the time, so manganese dissolves into the raw water. Manganese causes taste and odor complaints and stained fixtures, and it plugs the treatment plant's membrane filters. (PDF page 1) (opens in a new tab)

How high does manganese get?

Quarterly averages of total manganese ranged from 0.092 mg/l to 0.168 mg/l, and in early spring and early fall it can exceed 0.200 mg/l for several weeks, which rules out running the membrane filters. (PDF page 1) (opens in a new tab)

Did dissolved oxygen improve?

Yes. D.O. readings at the reservoir bottom just upstream of the dam show a dramatic increase once the Speece Cone® system went into service. (PDF page 2) (opens in a new tab)

The Project

Wolf Creek Reservoir

Location
Barberton, Ohio
Application
Reservoir Water Quality
Capacity
4,200 lbs/day
See the Project

In Full

More Key Figures

One more, each with what it measures and its PDF page.

From the PDF

FigureWhat It Measures
two systems
Superoxygenation systems installed on grade beside the reservoir (PDF page 2 (opens in a new tab))

Full Text as Published

The text as its authors wrote it.
The case study's own words, as published. Its figures are the authors'; the PDF (2 pages) is the original, with the figures, photos and tables drawn as images.

Breathing New Life into Lakes & Rivers Through SuperOxygenation

Reduced organics, nutrients, iron & manganese, harmful algal blooms.

The City of Barberton's Wolf Creek Dam Intake Extension, Valve Replacement and Oxygenation System Project is intended to rehabilitate the existing Wolf Creek Dam Water Intake Structure and install oxygenation equipment in the reservoir.

The new oxygenation system is being installed to improve the raw water quality being transported to the water treatment plant. The hypolimnion of the Wolf Creek Reservoir exhibits anoxic conditions during a majority of the time. This condition enables manganese to be taken up and transported in the dissolved form in the raw water. Manganese must be removed as it causes taste and odor complaints and staining of plumbing fixtures. The final source water quality parameter of interest is total manganese. Quarterly averages in total manganese have been found to range from 0.092 mg/l to 0.168 mg/l. More importantly, manganese has been identified as a source of plugging of the membrane filtration treatment system installed in the water treatment plant. Problematic times of the year are early spring and early fall when manganese can increase to concentrations over 0.200 mg/l for several weeks at a time, thus eliminating the option to run the membrane filters.

Aerial View of Barberton Reservoir, Denver, OH.

ECO₂ System Installation

The ECO₂ SuperOxygenation System is sized for a maximum oxygen feed rate of 2,000 lbs / day. The two Systems are installed on grade in a building adjacent to the reservoir. Intake and discharge piping bring and deliver oxygenated water to the reservoir hypolimnion.

The graph in the PDF shows the D.O. readings taken at the reservoir bottom just up-stream of the dam. There is a dramatic increase of hypolimnion D.O. once the Speece Cone system was put into service.

Chart: Barberton DO Increase at Start-Up.

How to Cite

One line to paste into a report.

Lake D.O. Supplementation at Barberton Reservoir in Denver OH. ECO₂. Project engineer: Burgess & Niple. Eco Oxygen Technologies Technical Library. https://eco2tech.com/technical-library/lake-d-o-supplementation-at-barberton-reservoir-in-denver-oh/

https://eco2tech.com/technical-library/lake-d-o-supplementation-at-barberton-reservoir-in-denver-oh/

The Next Step

Ask an ECO₂ Engineer

Questions about this case study, or about your own water? An application engineer answers, with the figures.

Lake Hodges, a reservoir among dry hills near San Diego, California