ECO₂ Wastewater Oxygenation

ECO₂'s wastewater brochure: what dissolving pure oxygen into raw wastewater does in sewer mains, headworks and primary clarifiers, and how the systems are sized.

Details

Publisher
ECO₂
Published
May 2023

Summary

ECO₂'s wastewater brochure explains how the Speece Cone® dissolves pure oxygen into a side stream of raw wastewater to stop sulfide from forming in sewer mains, headworks and primary clarifiers. It also notes that the same aerobic conditions prevent methane from forming.

Key Figures

Questions

How does the Speece Cone prevent sewer odors?

A side stream of raw wastewater is pumped through the Speece Cone, a down-flow oxygen contactor, where oxygen gas is added. The cone shape and the velocity gradient it creates dissolve all of the oxygen before the water returns to the pipe or basin, and the aerobic conditions prevent H₂S from forming. (PDF page 2) (opens in a new tab)

What flows and oxygen levels can a system handle?

Flows from 250 gpm to 25,000 gpm and dissolved oxygen from 30 mg/L to 300 mg/L, with 95% oxygen transfer efficiency at all feed rates and solids up to 4 inches. (PDF page 2) (opens in a new tab)

Why prevent H₂S in the liquid rather than treat the air?

H₂S corrosion happens in the vapor phase, and even 1 to 3 ppm of H₂S quickly damages concrete and metal. Preventing H₂S in the liquid with aerobic conditions eliminates that corrosion. (PDF page 2) (opens in a new tab)

Where does the oxygen come from?

It can be generated onsite or bought from a local gas supplier. (PDF page 2) (opens in a new tab)

Does oxygenation help with greenhouse gases?

Yes. The aerobic conditions that prevent odor and corrosion also prevent methane from forming, and the brochure notes methane is 30 times more harmful than CO₂. (PDF page 2) (opens in a new tab)

In Full

More Key Figures

Four more, each with what it measures and its PDF page.

From the PDF

FigureWhat It Measures
300 mg/L
Top of the dissolved oxygen range (range starts at 30 mg/L) (PDF page 2 (opens in a new tab))
1 to 3 ppm
H₂S levels that already cause rapid deterioration of concrete and metal (PDF page 2 (opens in a new tab))
4 inch
Solids the system passes without clogging (up to) (PDF page 2 (opens in a new tab))
30 times
How much more harmful methane is than CO₂ as a greenhouse gas (PDF page 2 (opens in a new tab))

Full Text as Published

The text as its authors wrote it.
The brochure's own words, as published. Its figures are the authors'; the PDF (4 pages) is the original, with the figures, photos and tables drawn as images.

Speece Cone Wastewater Oxygenation: Odor and Corrosion Prevention, Supplemental D.O., Effluent D.O.

Dr. Richard Speece, Inventor and Technical Advisor. Speece Cone Installation, Savannah Harbor.

Environmental Solutions with Pure Oxygen: The Clean Alternative for Odor and Corrosion Control

Superoxygenation is a high concentration dissolved oxygen technology for preventing anoxic conditions in a variety of water and wastewater applications, using pure oxygen as an alternative to aeration or chemicals.

H2S PREVENTION | PROCESS D.O. | EFFLUENT D.O.

Prevent sulfide formation in sewer mains, headworks, and primary clarifiers.

A side stream of raw wastewater is pumped through a down-flow oxygen contactor, called the Speece Cone, where oxygen gas is introduced. The cone-shaped geometry and the resulting velocity gradient ensure all oxygen is fully dissolved before returning to the pipe or basin.

A Speece Cone is at the heart of every ECO₂ system, each custom designed to satisfy the oxygen demand of a specific process or length of pipe.

  • Flow: 250 gpm - 25,000 gpm
  • D.O.: 30 mg/L - 300 mg/L
  • No bubbles. No air-locking.
  • No fouling. Consistent results.
  • No clogging. Up to 4-inch solids.
  • Compact footprint.
  • Guaranteed performance.
  • 95% OTE at all feed rates.

Improved Results

Aerobic conditions support rapid oxidation of reduced sulfur compounds, and prevent H2S formation in wastewater.

Field data shows H2S measured at the end of a sewer force main, over a 24-hr period. H2S rapidly drops to zero after startup of the ECO₂ system, installed at the pump station upstream.

Annual Savings

Oxygen gas is roughly 10 times less expensive than traditional chemicals for odor control. The annual chemical savings quickly offset the initial expense for equipment and installation.

Example Cost Comparison: $4.5 million saved over 20 years. (Based on 1,000 lbs/day NO2-O2 equivalent)

Since O2 has no byproducts or added solids, other processes downstream may benefit from reduced usage of nitrate or iron-based chemicals.

Asset Protection

H2S corrosion occurs in the vapor phase. Even low H2S levels (1-3 ppm) cause rapid deterioration of concrete and metal structures. Corrosion can be eliminated with aerobic H2S prevention in the liquid phase.

Environmental Sustainability

Methane is a greenhouse gas, 30 times more harmful to the environment, than CO2. Aerobic conditions intended to prevent odor and corrosion, also prevent the formation of methane.

ECO₂ project awards include the Envision Silver Award for Infrastructure Sustainability.

Automated Controls

ECO₂'s patented oxygen flow controls completely automate the oxygen feed process and system operation.

Oxygen Supply

Oxygen gas is easily generated onsite, or purchased from a local gas supplier. Both options make high-purity oxygen gas simple and affordable.

Installation Simplified

Packaged systems are pre-assembled with convenient field connections for wastewater, power, and oxygen.

How to Cite

One line to paste into a report.

ECO₂ Wastewater Oxygenation. ECO₂, May 2023. Eco Oxygen Technologies Technical Library. https://eco2tech.com/technical-library/eco2-wastewater-oxygenation/

https://eco2tech.com/technical-library/eco2-wastewater-oxygenation/

The Next Step

Ask an ECO₂ Engineer

Questions about this brochure, or about your own water? An application engineer answers, with the figures.

A rebuilt sewage pump station with a planted roof beside Lake Sammamish