Tech Bulletin - Oxygen Uptake Rate Test Procedure

An ECO₂ tech bulletin that sets out, step by step, how to run an oxygen uptake rate test to measure how fast a wastewater sample uses oxygen.

Details

Publisher
ECO₂

Summary

ECO₂'s two-page procedure for the Oxygen Uptake Rate (OUR) test, which measures how fast a wastewater sample consumes oxygen. The sample is oxygenated with pure oxygen to 20 mg/L, sealed in a BOD bottle with a D.O. probe, and read every 5 minutes for up to an hour. The slope of the D.O. line over time is the oxygen consumption rate; the worked example gives 0.15 mg/L per minute.

Key Figures

Questions

What does the Oxygen Uptake Rate (OUR) test measure?

The oxygen consumption rate of a sample of wastewater, read as the slope of dissolved oxygen against time in mg/L per minute. (PDF page 1) (opens in a new tab)

How is the wastewater sample prepared for an OUR test?

Collect a representative influent sample in an open container and oxygenate it with pure oxygen to 20 mg/L D.O., in less than 2 to 3 minutes to minimize oxygenation of sulfides. Then fill a BOD bottle completely, seal the D.O. probe into it and start the magnetic stirrer. (PDF page 1) (opens in a new tab)

How often are D.O. readings taken in the OUR test?

Every 5 minutes after the reading stabilizes, over a 1 hour period or until the D.O. runs out. (PDF page 1) (opens in a new tab)

How is the oxygen uptake rate calculated from the readings?

Plot D.O. (mg/L) against time (minutes), draw the best-fit straight line, and take its slope. In ECO₂'s example the slope is 0.15 mg/L per minute. (PDF page 2) (opens in a new tab)

How can OUR test variability be reduced?

Run the analysis immediately and average several OUR tests over a 2 to 3 week period, because the nature and temperature of wastewater vary. (PDF page 2) (opens in a new tab)

In Full

More Key Figures

One more, each with what it measures and its PDF page.

From the PDF

FigureWhat It Measures
2 to 3 weeks
Period over which to average several OUR tests to allow for variability (PDF page 2 (opens in a new tab))

Full Text as Published

The text as its authors wrote it.
The technical paper's own words, as published. Its figures are the authors'; the PDF (2 pages) is the original, with the figures, photos and tables drawn as images.

The Oxygen Uptake Rate (OUR) test is used to determine the oxygen consumption rate of a sample of wastewater.

Material needed

  • D.O. meter
  • BOD bottles
  • Oxygen source
  • Bubble diffuser
  • Thermometer
  • Timer

Preparation of sample

Collect a representative sample of the influent wastewater in an open container. Oxygenate the sample using pure oxygen until the sample D.O. is 20 mg/L. This should be done in less than 2 to 3 minutes to minimize oxygenation of sulfides.

Transfer the oxygenated water to the BOD bottle filling it completely. Insert the D.O. probe into the BOD bottle, making sure that the probe tightly seals the liquid from the atmosphere. Activate the magnetic stirrer. Note: adequate mixing is essential.

Measure oxygen consumption rate

Record D.O. readings

After the meter reading has stabilized, record the initial D.O. reading. Record levels at time intervals of 5 minute. Record data over a 1 hour period or until the D.O. is less zero.

Calculations

Plot the observed readings (D.O. mg/L vs time in minutes) on regular graph paper. Draw a straight line that best fits all points. If using a computer to develop the graph, draw a linear trendline.

Example of data and a graph

Time (minutes)D.O. (mg/L)
020.9
519.1
1018.5
1518.3
2017.6
2517.1
3016.7
3515.9
4014.7
4513.8
5013.2
5511.3
6010.2

Determining the slope

Now determine the slope of the line by using the equation m = (y - b) / x

where:

  • y = y intercept
  • x = x intercept
  • m = slope
  • b = where line crosses y axis

Note: To choose x and y, it is best to use a point that intersects the trendline.

The following steps demonstrate how the slope (m) is calculated:

m = (y - b) / x = (13.8 – 20.7) / 45 = - 0.15 mg/L/min

The slope represents the oxygen consumption rate in mg/L per minute.

Variability compensation

Variability in the nature and temperature changes of the wastewater will result in variability with performance of the OUR test. Analysis should be conducted immediately. Also, to compensate for variability, it is highly recommended to take the arithmetic mean of at least multiple OUR tests over a 2-3 week period.

How to Cite

One line to paste into a report.

Tech Bulletin - Oxygen Uptake Rate Test Procedure. ECO₂. Eco Oxygen Technologies Technical Library. https://eco2tech.com/technical-library/tech-bulletin-oxygen-uptake-rate-test-procedure/