Tech Bulletin - Oxygen Demand and Solubility Calculations

An ECO₂ tech bulletin gathering the published methods for calculating how much oxygen wastewater needs and how much oxygen it can hold in solution.

Details

Publisher
ECO₂

Summary

ECO₂'s design basis for Superoxygenation systems, with the references behind it. It takes 2 mg/L of dissolved oxygen to oxidize each 1 mg/L of dissolved sulfide, the reaction takes 15 to 30 minutes, and wastewater consumes 5 to 15 mg/L of oxygen an hour.

Key Figures

Questions

How much oxygen is needed to oxidize dissolved sulfide in wastewater?

2 mg/L of dissolved oxygen for every 1 mg/L of dissolved sulfide, a 2:1 ratio ECO₂ has verified in the field many times. (PDF page 1) (opens in a new tab)

How long does it take dissolved oxygen to oxidize sulfide?

Dissolved sulfides are metabolized within 15 to 30 minutes, so ECO₂ installs systems at least 30 minutes of hydraulic retention time upstream of the area needing odor control. (PDF page 2) (opens in a new tab)

What is the oxygen uptake rate of raw wastewater?

Between 5 and 15 mg/L per hour according to U.S. EPA references, depending mainly on temperature, BOD and retention time. (PDF page 2) (opens in a new tab)

How does pressure change oxygen solubility in a Superoxygenation system?

Using the Benson and Krause equations, saturation rises by approximately 1 mg/L of dissolved oxygen for every foot of head at typical wastewater temperatures of 20 to 25 ℃. (PDF page 2) (opens in a new tab)

In Full

More Key Figures

Two more, each with what it measures and its PDF page.

From the PDF

FigureWhat It Measures
5 to 15 mg/L per hour
Oxygen uptake rate of wastewater (U.S. EPA references, validated by ECO₂) (PDF page 2 (opens in a new tab))
1 mg/L per foot of head
Approximate rise in dissolved oxygen saturation for each foot of head pressure at 20-25 ℃ (PDF page 2 (opens in a new tab))

Full Text as Published

The text as its authors wrote it.
The technical paper's own words, as published. Its figures are the authors'; the PDF (3 pages) is the original, with the figures, photos and tables drawn as images.

ECO₂ SuperOxygenation system design: literary references

Amount of dissolved oxygen required to oxidize dissolved sulfide

In biochemical oxidation of organic matter, free oxygen as dissolved oxygen (D.O.) is the preferred electron acceptor (1). Dissolved sulfides (D.S.) are oxidized to sulfur and sulfate according to the following reactions (2)(3):

  • 2 H₂S + O₂ → 2 H₂O + 2 S
  • H₂S + 2 O₂ → 2 H + SO₄

Per these equations, it takes 2 mg/L of D.O. for every 1 mg/L of dissolved sulfide present in the wastewater. ECO₂ SuperOxygenation systems are designed to add this ratio of D.O. to D.S. to ensure that the D.S. are fully oxidized. It is important to note that this 2:1 oxygen to dissolved sulfide requirement has been verified by ECO₂ in the field numerous times in operating systems across the country.

Amount of time required to oxidize dissolved sulfide

When H₂S is in the presence of D.O., biochemical oxidation occurs and dissolved sulfides are metabolized within 15-30 minutes. Figure 1 (7) represents the first order reaction of sulfide oxidation as derived through numerous wastewater tests conducted by Alan Plummer and Associates, Inc.

Figure 1 is in the PDF.

ECO₂ systems are designed to be installed at least 30 minutes of Hydraulic Retention Time (HRT) upstream of the area requiring odor control. This ensures that there is a sufficient amount of time for the D.S. to be oxidized in the wastewater before it can be released.

Amount of dissolved oxygen required to maintain aerobic conditions

The oxygen uptake rate of wastewater is a function of several wastewater parameters, most importantly temperature, BOD level and HRT. It has been well documented in a number of U.S. EPA references that the oxygen uptake rate of wastewater ranges between 5-15 mg/L per hour (1)(2). ECO₂, through extensive field testing across its installation base, has validated this range and has developed tools to accurately predict the oxygen uptake rate in different systems.

Oxygen saturation tables listed by temperature and atmospheric pressure are contained in numerous textbooks and other publications. Typically, these tables are valid for water in contact with air. The WEF Manual of Practice 25 contains a graph of how the oxygen saturation of water changes with pressure when water is in contact with pure oxygen rather than air.

Figure 2 is in the PDF.

Considering Henry's Law where p=kHc, if the partial pressure of oxygen in air is increased from 0.21 atm to 0.93 atm using high purity oxygen, the saturation of oxygen in water at 20℃ at sea level will increase from 9.1 mg/L to 40.3 mg/L.

ECO₂ has developed analytical tools which utilize the Benson and Krause equations (4) for calculating the solubility of oxygen in water. The pressure factor portion of the equation considers temperature, barometric pressure, water vapor pressure and the second virial coefficient of oxygen to correct for non-ideal gas behavior. The result is in proportion to the graph in Figure 2. and is approximately 1 mg/L increase in D.O. for every 1 foot of head pressure increase at typical wastewater temperatures of 20-25 ℃.

The ECO₂ SuperOxygenation concept and installations in print

The ECO₂ SuperOxygenation concept and projects have been well documented in a number of academic books, engineering journals and trade publications. The Metcalf and Eddy Wastewater Engineering Treatment and Reuse (5) text as well as Dr. Richard Speece's Anaerobic Biotechnology and Odor/Corrosion Control for Municipalities and Industries (6) both describe the use of oxygen in conjunction with the ECO₂ SuperOxygenation systems. Other references are readily available upon request.

References

  1. U.S. Environmental Protection Agency (1985) Design Manual, Odor and Corrosion Control in Sanitary Sewerage Systems and Treatment Plants; EPA-625/1-85-018, U.S. Environmental Protection Agency: Washington, D.C., page 4.
  2. U.S. Environmental Protection Agency (1974) Process Design Manual for Sulfide Control in Sanitary Sewerage Systems; U.S. Environmental Protection Agency: Washington, D.C., page 3-19, 3-22, 5-4.
  3. Water Environment Federation (2004) Control of Odors and Emissions from Wastewater Treatment Plants; WEF Manual of Practice 25, Water Environment Federation; Alexandria, VA, page 258, 262.
  4. Benson, B.B., and Daniel Krause, Jr (1984) The concentration and isotopic fractionation of oxygen dissolved in freshwater and seawater in equilibrium with the atmosphere: Limnology and Oceanography, vol. 29, no. 3, p. 620-632.
  5. Tchobanoglous, George (2003) Wastewater Engineering Treatment and Reuse, 4th ed. Metcalf & Eddy, Inc. New York, NY.
  6. Richard Speece, (2008) Anaerobic Biotechnology and Odor/Corrosion Control, Archae Press, Nashville, TN.
  7. Alan Plummer and Associates, Inc. derived formula through wastewater testing.

How to Cite

One line to paste into a report.

Tech Bulletin - Oxygen Demand and Solubility Calculations. ECO₂. Eco Oxygen Technologies Technical Library. https://eco2tech.com/technical-library/tech-bulletin-oxygen-demand-and-solubility-calculations/