El Paso, TX Frontera Lift Station Replaces Chemical Feed System with Oxygen
Estudo de caso da ECO₂: na Frontera Lift Station de El Paso, o oxigênio substituiu a dosagem de produtos químicos numa longa linha de recalque dupla, com custo menor e H₂S baixo.
Detalhes
Resumo
A El Paso Water Utilities tinha odor e corrosão elevados na sua Northwest WWTP porque as 3,5 milhas de linha de recalque dupla que vêm da Frontera Pump Station entregavam esgoto com até 20 mg/L de H₂S. Um estudo da CH2MHill comparou cinco produtos químicos de controle de odor, a ozonização e a Superoxigenação, e escolheu o sistema da ECO₂ pelo menor custo de ciclo de vida.
Números-chave
12ppm
H₂S médio com dosagem de nitrato de cálcio 1ppm
H₂S médio com oxigênio 95%
Eficiência média de transferência de oxigênio
Perguntas
Por que a Northwest WWTP tinha problemas de odor?
Mais de 90% da sua vazão chega pela linha de recalque dupla de 3,5 milhas que vem da Frontera Pump Station. Tempos de detenção de mais de 12 horas, em certos momentos, produziam H₂S na fase líquida de até 20 mg/L, o que causava odor e corrosão elevados. (PDF, página 1) (abre em nova aba)
Que opções El Paso comparou?
A CH2MHill comparou cinco produtos químicos tradicionais de controle de odor, a ozonização e a Superoxigenação. O sistema da ECO₂ teve o menor custo de ciclo de vida e foi instalado na Frontera Pump Station, a montante da estação de tratamento. (PDF, página 1) (abre em nova aba)
Como o oxigênio dissolvido acaba com o H₂S?
Ele reage com os sulfetos já presentes e cria condições aeróbias que impedem a formação de mais. O sistema dissolve oxigênio puro com eficiência média de transferência de oxigênio de 95%. (PDF, página 2) (abre em nova aba)
O projeto

Frontera Pump Station
Na íntegra
Mais números-chave
Mais quatro, cada um com o que mede e sua página no PDF.
Do PDF
| Número | O que mede |
|---|---|
| 20 mg/L | H₂S na fase líquida antes do tratamento (até) (Página 1 do PDF (abre em nova aba)) |
| 3,5 milhas | Comprimento da linha de recalque dupla de Frontera (Página 1 do PDF (abre em nova aba)) |
| 90% | Parcela da vazão da ETE vinda da Frontera Pump Station (mais de) (Página 1 do PDF (abre em nova aba)) |
| 17,5 MGD | Capacidade de projeto da Northwest WWTP (Página 1 do PDF (abre em nova aba)) |
Texto completo como publicado (em inglês)
O texto como seus autores o escreveram.
El Paso Water Utilities operates the Northwest WWTP which was built with a 17.5 MGD capacity, but currently with an average daily flow of 9-10 MGD. Odor emissions at the plant are directly related to the wastewater entering the front end of the plant from the collection system, mainly the 3.5-mile dual force main from the Frontera Pump Station (which conveys over 90% of the plant's flow). The high HRT (over 12 hours at times) results in extremely high H2S concentrations of up to 20mg/L in the liquid phase, which causes excessively high odors and corrosion rates.
With the WWTP adjacent to the busy Interstate-10 and a new housing development, El Paso Water Utilities hired CH2MHill to study, design, and manage the construction of odor improvements at the Northwest WWTP.
Their study included a comparison of five traditional odor control chemicals, ozonation, and SuperOxygenation. Based on lowest life-cycle costs, the SuperOxygenation System by ECO₂ was chosen and installed at the Frontera Pump Station, upstream of the plant.
Pictured: SuperOxygenation System's Speece Cone Oxygen Transfer Reactor installed at Frontera Pump Station, El Paso, TX.
At 40% of the cost, the ECO₂ System lowers the average H2S level from 12 ppm with calcium nitrate feed, to 1 ppm with oxygen.
The ECO₂ SuperOxygenation System dissolves pure oxygen into wastewater at an average oxygen transfer efficiency of 95%. Dissolved Oxygen readily reacts with existing sulfides and prevents further formation of sulfides by creating aerobic conditions. Eliminating H2S not only prevents odor, but also, prevents costly corrosion of pipes and treatment plant equipment.
Chart: H2S Concentration at Discharge of Frontera Dual Force Main, March 2015 to May 2015, SuperOxygenation compared with Calcium Nitrate Feed.
Como citar
Uma linha para colar em um relatório.
El Paso, TX Frontera Lift Station Replaces Chemical Feed System with Oxygen. ECO₂. Project engineer: Jacobs (CH2M). Eco Oxygen Technologies Technical Library. https://eco2tech.com/technical-library/el-pasotx-frontera-lift-station-replaces-chemical-feed-system-with-oxygen/
https://eco2tech.com/technical-library/el-pasotx-frontera-lift-station-replaces-chemical-feed-system-with-oxygen/
O próximo passo
Pergunte a um engenheiro da ECO₂
Dúvidas sobre este estudo de caso ou sobre a sua água? Um engenheiro de aplicações responde, com os números.