St. Petersburg, FL Lift Stations Odor and Corrosion Control

Estudo de caso da ECO₂: em St. Petersburg, Flórida, Speece Cones® em duas elevatórias evitam o H₂S em longas linhas de recalque e reduzem odor e corrosão na estação de tratamento.

Detalhes

Publicado por
ECO₂
Publicação
abril de 2025

Resumo

A Southwest Water Reclamation Facility de St. Petersburg trata cerca de 20 MGD, alimentada por duas grandes linhas de recalque que saem das Lift Stations 28 e 85 e que, de outro modo, gerariam sulfeto de hidrogênio, odor e corrosão. Como parte da iniciativa de sustentabilidade da cidade, os sistemas ECO₂ Speece Cone de Superoxigenação com suprimento de oxigênio líquido substituíram os produtos químicos tradicionais de controle de odor. A Lift Station 28 (instalada em 2024) trata uma linha de recalque de 20 polegadas e 3 milhas com 1.100 lb/dia de oxigênio puro; a Lift Station 85 (instalada em 2023) trata uma linha de recalque de 30 polegadas e 7 milhas com 3.300 lb/dia. Os dois cones têm 5 pés de diâmetro.

Números-chave

Perguntas

Por que St. Petersburg adicionou oxigênio a essas linhas de recalque?

As duas linhas de recalque que alimentam a Southwest Water Reclamation Facility produziriam, de outro modo, H₂S em quantidade significativa, causando odor e corrosão, e a cidade queria reduzir o uso de produtos químicos dentro da sua iniciativa de sustentabilidade. (PDF, página 1) (abre em nova aba)

O que foi instalado na Lift Station 28?

Um Speece Cone da ECO₂ de 5 pés com suprimento de oxigênio líquido, que dissolve 1.100 lb/dia de oxigênio puro em uma linha de recalque de 20 polegadas e 3 milhas; instalado em 2024. (PDF, página 1) (abre em nova aba)

O que foi instalado na Lift Station 85?

Um Speece Cone da ECO₂ de 5 pés com suprimento de oxigênio líquido, que dissolve 3.300 lb/dia de oxigênio puro em uma linha de recalque de 30 polegadas e 7 milhas; instalado em 2023. (PDF, página 2) (abre em nova aba)

Que resultados o estudo de caso lista?

Custos reduzidos, odores eliminados e infraestrutura protegida. (PDF, página 2) (abre em nova aba)

Os projetos

Lift Station 28

Local
St. Petersburg, Flórida
Aplicação
Controle de odor em esgoto
Capacidade
1.100 lb/dia
Veja o projeto

Lift Station 85

Local
St. Petersburg, Flórida
Aplicação
Controle de odor em esgoto
Capacidade
3.300 lb/dia
Veja o projeto

Na íntegra

Mais números-chave

Mais cinco, cada um com o que mede e sua página no PDF.

Do PDF

NúmeroO que mede
3.300 lb/dia
Oxigênio puro dissolvido na Lift Station 85 (Página 2 do PDF (abre em nova aba))
7 milhas de linha de recalque
Comprimento tratado a partir da Lift Station 85 (30 polegadas de diâmetro) (Página 2 do PDF (abre em nova aba))
5 pés
Diâmetro de cada Speece Cone (Página 1 do PDF (abre em nova aba))
2024
Ano de instalação do sistema da Lift Station 28 (Página 1 do PDF (abre em nova aba))
2023
Ano de instalação do sistema da Lift Station 85 (Página 2 do PDF (abre em nova aba))

Texto completo como publicado (em inglês)

O texto como seus autores o escreveram.
As palavras do próprio estudo de caso, como publicadas. Os números são dos autores; o PDF (2 páginas) é o original, com as figuras, fotos e tabelas em forma de imagem.

Case Study: Odor Control, Saint Petersburg, FL

Lift Station 28

The Southwest Water Reclamation Facility (SWWRF) processes about 20 million gallons per day (MGD) of wastewater for the City of St. Petersburg. The wastewater treatment plant is fed by two large force mains leaving Lift Station 28 and Lift Station 85. These two force mains if left untreated would cause significant Hydrogen Sulfide (H₂S) leading to odor and corrosion issues. As part of the City's sustainability initiative, an alternative to traditional odor control chemicals was needed to reduce chemical use and lower H₂S levels.

ECO₂ Speece Cone Superoxygenation system installed at Lift Station 28 Including Liquid Oxygen Supply (LOX) system.

ECO₂ Speece Cone Superoxygenation System

An ECO₂ Speece Cone Superoxygenation System was installed at Lift Station 28 to treat the 20" diameter, 3-mile long force main to prevent H₂S formation to reduce odors and corrosion at the SWWRF influent in the treatment plant. The ECO₂ Speece Cone is 5 feet in diameter and dissolves 1,100 lbs/day of pure oxygen.

ApplicationOdor & Corrosion Prevention
ConsultantSt. Petersburg Water Resources
O₂ Capacity1,100 lbs/day
O₂ SupplyLOX Storage Tank
Installed2024
Lift Station 85

The Southwest Water Reclamation Facility (SWWRF) processes about 20 million gallons per day (MGD) of wastewater for the City of St. Petersburg. The wastewater treatment plant is fed by two large force mains leaving Lift Station 28 and Lift Station 85. These two force mains if left untreated would cause significant Hydrogen Sulfide (H₂S) leading to odor and corrosion issues. As part of the City's sustainability initiative, an alternative to traditional odor control chemicals was needed to reduce chemical use and lower H₂S levels.

ECO₂ Speece Cone Superoxygenation system installed at Lift Station 85 Including Liquid Oxygen Supply (LOX) system.

ECO₂ Speece Cone Superoxygenation System

An ECO₂ Speece Cone Superoxygenation System was installed at Lift Station 85 to treat the 30" diameter, 7-mile long force main to prevent H₂S formation to reduce odors and corrosion at the SWWRF influent in the treatment plant. The ECO₂ Speece Cone is 5 feet in diameter and dissolves 3,300 lbs/day of pure oxygen.

ApplicationOdor & Corrosion Prevention
ConsultantSt. Petersburg Water Resources
O₂ Capacity3,300 lbs/day
O₂ SupplyLOX Storage Tank
Installed2023
  • Summary: Sewer Collections, St Petersburg, FL
  • Problem: Odor Complaints; H₂S Corrosion
  • Solution: Superoxygenation
  • Results: Reduced Costs; Odors Eliminated; Infrastructure Protected

Como citar

Uma linha para colar em um relatório.

St. Petersburg, FL Lift Stations Odor and Corrosion Control. ECO₂, April 2025. Eco Oxygen Technologies Technical Library. https://eco2tech.com/technical-library/st-petersburg-fl-lift-stations-odor-and-corrosion-control/

https://eco2tech.com/technical-library/st-petersburg-fl-lift-stations-odor-and-corrosion-control/